The hydraulic control valve is a hydraulic pressure control valve. The hydraulic control valve is composed of a main valve and its attached conduit, pilot valve, needle valve, ball valve, pressure reducing valve, slow closing check valve, flow control valve, pressure relief valve, Water power electric control valve, water pump control valve, etc. Filters should be installed before the hydraulic control valve, and the requirements for sewage discharge should be facilitated.
The 500X pressure relief / pressure valve king should be used in fire or other water supply systems to prevent system overpressure or maintain pressure on the fire water supply system. The impact of the water hammer can also be reduced after the fire pump is turned off. Also used in water hammer elimination devices for large water supply systems. And the inlet of the valve control system is equipped with a self-cleaning filter. The fluid characteristics make the suspended particles with larger specific gravity and larger diameter not enter the control system. Ensure that the system is unobstructed and the valve operates safely and reliably. The system operates smoothly, with high strength and long service life, and is suitable for pipelines up to 600 caliber. Valve structure features and uses.
The 500X pressure relief/pressure valve consists of a main valve, a pressure relief/pressure holding pilot needle valve, a ball valve, a microfilter and a pressure gauge to form a hydraulic control takeover system. It can be used as a pressure relief valve or as a pressure holding valve by hydraulic automatic operation. When used as a pressure relief valve, the water supply line pressure can be maintained below the set safety value; for the pressure holding valve, the upstream water pressure of the main valve can be maintained above the set value to maintain the upstream supply pressure of the main valve.
The 500X pressure relief/pressure valve utilizes hydraulic self-power control, requires no other equipment and energy, is easy to maintain, and is multi-purpose for one valve.
This series of 500X pressure relief / pressure valve products are widely used in high-rise buildings, living areas and other water supply pipe network systems and urban water supply projects.
500X pressure relief / pressure valve working principle
1. As a pressure relief valve: when the pressure relief/pressure holding pilot valve is adjusted to the pressure relief state, the water flows through the needle valve, the main valve control chamber, the ball valve A, the pressure relief/pressure holding pilot valve, and the ball valve B to the outlet. The main valve is open. When the inlet pressure exceeds the safe value set by the pressure relief/pressure holding pilot valve, the pressure relief pilot valve will automatically open, and part of the water is discharged through the ball valve C to relieve the pressure of the pipeline. The pressure relief valve automatically closes when the pressure returns to a safe value. When the pressure relief valve is used, each ball valve is normally open.
2. As the holding pressure valve: When the pressure relief/pressure holding pilot valve is adjusted to the holding pressure state, the pilot valve is closed as long as the main valve inlet water pressure is lower than the pilot valve setting value. The main control room is boosted and the main valve is closed. When the upstream supply pressure of the main valve exceeds the set pressure of the pilot valve, the holding pilot valve can be opened, the water in the control chamber is discharged to the outlet through the ball valve, and the main valve of the control chamber is opened, and the water supply is started, that is, the upstream water pressure is maintained. When used as a pressure holding valve, the ball valve C is normally closed or replaced with a wire plug.
500X pressure relief / pressure valve main technical parameters
Nominal pressure (Mpa) | Shell test pressure (MPa) | Seal test pressure (MPa) | Applicable medium | Medium temperature (°C) |
1.0 | 1.5 | 1.1 | water | 0-80 |
1.6 | 2.4 | 1.76 | ||
2.5 | 3.75 | 2.75 |
500X pressure relief / pressure valve main parts and materials
Part Name | Part material |
Valve body bonnet | WCB |
Seat valve disc | Copper alloy |
Seal O-ring | Nitrile rubber |
Valve stem | 2Cr13 |
spring | 50CrVA |
Needle valve | Copper alloy |
Ball valve | Copper alloy |
Pressure relief / pressure holding pilot valve | Copper alloy |
Micro filter | stainless steel |
500X pressure relief valve connection size (PN 1.0-2.5MPa):
Nominal diameter DN | L | H | H1 | A | B |
50 | 250 | 335 | 90 | 170 | 170 |
65 | 280 | 345 | 98 | 180 | 180 |
80 | 310 | 355 | 110 | 190 | 190 |
100 | 350 | 365 | 120 | 200 | 200 |
125 | 400 | 445 | 145 | 215 | 215 |
150 | 450 | 460 | 155 | 230 | 230 |
200 | 550 | 505 | 190 | 255 | 255 |
250 | 650 | 550 | 250 | 295 | 295 |
300 | 800 | 710 | 290 | 325 | 325 |
350 | 900 | 725 | 330 | 380 | 380 |
400 | 1000 | 760 | 360 | 415 | 415 |
450 | 1000 | 810 | 445 | 435 | 435 |
500 | 1100 | 865 | 495 | 460 | 460 |
600 | 1100 | 935 | 550 | 520 | 520 |
700 | 1450 | 1000 | 605 | 570 | 570 |
800 | 1560 | 1100 | 730 | 620 | 620 |
900 | 1800 | 1205 | 800 | 670 | 670 |
1000 | 2000 | 1330 | 910 | 830 | 830 |